IOTAFLOW Fire Pump Test Meter with differential pressure dial gauge on red carbon steel venturi body
IOTAFLOW Fire Pump Test Meter with differential pressure dial gauge on red carbon steel venturi body
Fire pump test meter dial gauge reading flow (m3/h) and differential pressure (mmWC)
Fire pump test meter technical drawing - front and side view

Fire Protection

Fire Pump Test Meter

IOTAFLOW Fire Pump Test Meter – Direct-Reading Flow Testing for Fire Pump Systems

  • UL certified fire pump test meter for accurate, repeatable flow testing.
  • Carbon steel body, ±2% FS accuracy, grooved/ANSI/butt weld ends, rated up to 34.5 bar (500 psi).
  • Direct-reading dual-scale dial (LPM/GPM & ΔP) with no external power required.
  • Fire ProtectionFire Protection
    No Power RequiredNo Power Required
    Direct-Reading DialDirect-Reading Dial

A fire pump is only as dependable as its last flow test. The IOTAFLOW Fire Pump Test Meter is a differential pressure flow meter built specifically for fire pump performance testing. Installed permanently in the pump's test line, it lets maintenance teams confirm that the pump is delivering its rated flow (LPM/GPM) – quickly, safely, and without setting up hoses, nozzles and pitot gauges for every test.

The meter combines a carbon steel venturi-type flow body with a differential pressure gauge (Buna convoluted diaphragm), connected through ¼" brass ball valves. Its dual-scale dial shows flow rate and differential pressure directly – no charts, conversions or external power needed. It is available with Grooved, ANSI 150, ANSI 300 and Butt Weld connections, in line sizes from DN100 to DN250, and is UL certified for fire protection service.

Ideal for fire protection contractors, facility managers and plant safety teams who need reliable, repeatable flow data during commissioning, acceptance tests and routine fire pump testing.

How to Test a Fire Pump with the Fire Pump Test Meter

The test meter is installed in the pump's by-pass test line, with at least 5 pipe diameters (5D) of straight pipe before it and 2 pipe diameters (2D) after it, between the by-pass valve and the throttle valve that discharges to waste. Follow these operating instructions for each flow test:

  1. Close the system valve.
  2. Open the system by-pass valve and the throttle valve.
  3. Purge air from the meter:
    • Open the shut-off valves and vent valves on the meter.
    • When a steady stream of water is passing through each hose, the meter is purged of air.
    • Close the vent valves after purging.
  4. Refer to the pump's rated GPM/LPM requirement and adjust the throttle valve to reach it, then read the flow directly on the dial.
  5. After the test, open the system valve and close the system by-pass and throttle valves.
Fire pump typical piping diagram showing test meter location with 5xD and 2xD straight pipe, by-pass valve, throttle valve and system valve
Fire pump typical piping: the test meter sits in the by-pass test line, 5D downstream of the by-pass valve and 2D upstream of the throttle valve.

Applications

  • Periodic & Annual Fire Pump Testing – Performance checks at rated (100%) and peak (150%) flow points, in line with NFPA 20 / NFPA 25 practice
  • Commissioning & Acceptance Tests – Verifying new fire pump installations before handover
  • High-Rise & Commercial Buildings – Residential towers, malls, hotels, hospitals and IT parks
  • Industrial Plants – Refineries, petrochemical, power, chemical and pharmaceutical facilities
  • Warehouses & Data Centres – Logistics parks, cold storage and mission-critical facilities
  • Infrastructure Projects – Airports, metro rail, tunnels and SEZs
  • Fire Hydrant & Sprinkler Pump Sets – Flow verification on fire water ring mains and pump houses